Customization: | Available |
---|---|
Application: | High-performance Transducer, Three Phase Transducer, High Frequency Converter Transducer |
Output Type: | Triple |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
High precision 3 hp vfd inverter 3 phrase with rated current 5.1A at 380V ~ 480V, 9A at 220V ~ 240V, works at (-10ºC, 40ºC). IP 20 enclosure protection, sensorless vector control mode. Widely used in transformers, electronic ballasts, AC fans, uninterruptible power systems, chargers, relays, compressors, motors, etc.
Basics | Model | G630-4T2.2GB |
Capacity | 2.2 kW (3 hp) | |
Shipping weight | 3 kg | |
Dimension | ||
I/O Feature | Rated current | 5.1A at 380V ~ 480V, 9A at 220V ~ 240V |
Input voltage | 3 phase 220V /380V /480V AC ±15% (Optional) | |
Input frequency | 50Hz/ 60Hz | |
Output voltage | 3 phase AC 0~input voltage | |
Output frequency | 0~1000Hz | |
Over load capacity | 150% of rated current for 1 minute, 180% of rated current for 3 seconds | |
Control Feature | Control mode | V/F control; Sensorless vector control; |
Communication | RS485 | |
Speed regulation | 1:100 | |
Start torque | 150% of rating torque at 1 Hz | |
Speed control accuracy | ≤±0.5% of rating synchronous speed | |
Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% |
|
Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz |
|
Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% | |
Interior PID controller | Be convenient to make closed-loop system | |
Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running | |
Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. | |
Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip | |
Environment | Enclosure rating | IP 20 |
Temperature | -10ºC~ +40ºC; VFD will be derated if ambient temperature exceed 40ºC; each rise 1ºC, the derate will be 5% | |
Humidity | 5%-95%, without condensation | |
Altitude | ≤1000m; VFD will be derated if above 1000m | |
Impingement and oscillation | Normal running: 5.9m/s2 (0.6g); Transportation: 15m/s2 (1.5g) | |
Store environment | -20ºC~ +60ºC; no dust, no corrosive gas, no direct sunlight |