Customization: | Available |
---|---|
Application: | High Frequency Converter Transducer |
Output Type: | Triple |
Still deciding? Get samples of US$ 59.99/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Specifications | ||
Maximum frequency | Vector control: 0~600Hz VF control: 0~1200Hz |
|
Carrier frequency | 1k~15kHz: The carrier frequency can be adjusted automatically according to the load characteristics. | |
Input frequency resolution | Digital setting: 0.01Hz Analog setting: Maximum frequency × 0.1% |
|
Control method | Open-loop vector control (SVC), V/F control | |
Starting torque | G-model: 0.5Hz/180% (open-loop vector control) P-model: 0.5Hz/120% (open-loop vector control) |
|
Speed range | 1:200 (open-loop vector control) | |
Speed stabilization accuracy (Speed control accuracy) |
Open-loop vector control: ≤±0.5% (rated synchronous speed) | |
Speed control stability | Open-loop vector control: ≤±0.3% (rated synchronous speed) | |
Torque response | ≤40ms (open loop vector control) | |
Overload capacity | Model G: 150% of rated current for 60 seconds; 180% of rated current for 5 seconds Model P: 120% of rated current for 60 seconds; 150% of rated current for 5 seconds |
|
Torque Increase | Torque increase automatically Torque increase 0.1% to 30.0% manually |
|
V/F curve | Three types: linear; multi-point; squared V/F curve | |
Acceleration/Deceleration curves | Linear or S-curve acceleration and deceleration mode; Four kinds of acceleration and deceleration time; Acceleration and deceleration time range 0.0s~3000.0s | |
DC Brake | DC braking frequency: 0.0Hz~maximum frequency Braking time: 0.0~36.0 seconds Braking action current value: 0.0%~100.0% |
|
Jog control | Point-to-point frequency range: 0.00Hz~50.00Hz; Jog acceleration and deceleration time 0.0s~3000.0s |
|
Simple PLC Multispeed operation |
Up to 16 speeds via built-in PLC or control terminals | |
Built-in PID | Process control closed-loop control system can be realized easily | |
Automatic Voltage Regulation (AVR) | Keep the output voltage constant when the grid voltage changes automatically | |
Torque limiting and control | "Digger" feature: torque limiting during operation to prevent frequent overcurrent trips automatically; Closed-loop vector mode for torque control |
|
Power-up peripherals safety self-test | Power-on safety detection of peripheral devices such as grounding, short-circuiting, etc. can be realized | |
Common DC bus function | Realize the function of DC bus shared by multiple inverters | |
JOG key | Programmable key: Forward and reverse operation/spot operation function selection | |
Textile swing control | Various triangle wave frequency control functions | |
Fast current limit function | Built-in fast current limiting algorithm Reduces the probability of overcurrent reported Improves the anti-interference ability |
|
Timing control | Function: Setting time range 0h~65535h | |
Standardization of keyboard extension cables | Customers may extend the keyboard by using a standard network cable | |
Run |
Run command channel | Three types of channels: operator panel given, control terminal given, and serial communication port given. Switchable in various ways |
Frequency source | 10 types of frequency sources: digital, analog voltage, analog current, pulse, and serial port give and take. Switchable in various ways | |
Auxiliary frequency sources | 10 kinds of auxiliary frequency sources. Realization of auxiliary frequency trimming and frequency synthesis flexible. |
|
Input terminal | Standard seven digital input terminals, up to nine digital input terminals (AI1, AI2 can be used as X (DI) terminals), compatible with active PNP or NPN input. Two analog input terminals, of which AI1 can only be used as a voltage input and AI2 can be used as a voltage or current input. |
|
Output terminal | One digital output terminal (bipolar output) Two relay output terminals Two analog output terminals, can be selected from 0/4mA to 20mA or 0/2V to 10V respectively, which can realize the output of physical quantities such as set frequency, output frequency and rotational speed. |
|
Display and keyboard operation | LED display | Display parameters |
LCD display | Optional, Chinese/English prompts for operation content | |
LCD parameter copy | Quick copying of parameters using the LCD | |
Key lock and function selection | Partial or full locking of keys, defining the scope of action of some keys to prevent misoperation. | |
Protection and Options | Protective function | Power-on motor short-circuit detection, input and output phase loss protection, over-current protection, over-voltage protection, under-voltage protection, over-heating protection, overload protection, etc. |
Optional accessories | LCD operation panel, brake unit, etc. | |
Location | Indoors, out of direct sunlight, free of dust, corrosive gases, flammable gases, oil mist, water vapor, dripping water or salt, etc. | |
Altitude | Please use at a reduced rate (below 1000 meters, above 1000 meters) |
|
Environmental temperature | -10ºC~+50ºC (please use at a reduced rating 40ºC~50ºC) |
|
Humidity level | Less than 95% RH, no water droplet condensation | |
Vibratory | Less than 5.9 m/s2 (0.6 g) | |
Storage temperature | -20ºC~+60ºC | |
Contamination level | 2 | |
Product standard | Product implementation of safety standards | IEC 61800-5-1:2007 |
Product implementation of EMC standards | IEC 61800-3:2005 |